Pressure Limiting and Regulating Stations: Inspection, Testing, Reliefs, etc. (17.10)
Criticality: Medium
Progress: Addressed, Not Adequately
Score: 12
DOT Relevance: §192.739 – §192.743
Description of Key Area
Sections 192.739 to 192.743 of Subpart M (Maintenance) of 49 CFR
192 address pressure limiting and regulating stations. The equipment at the
stations must be inspected at certain and regular time intervals to make sure
that their condition is adequate and can support the capacity required. The
equipment must also be checked to make sure that it is set at the correct
pressure. Sometimes, the regulating stations must be equipped with telemetering
or recording pressure gauges to indicate the gas pressure in the district. If there
is an indication of an abnormally high or low pressure, corrective measures are
taken. Pressure relief devices must be tested “in place” at regular intervals.
Discussion of Criticality
For hydrogen pipeline purposes, relief devices are important.
Regulations as to the frequency of inspection must be determined. The necessity
of telemetering to indicate gas pressure on the hydrogen pipeline must be
determined. Necessary steps must be put in place when there are indications of
abnormally high or low pressure in the hydrogen system. The frequency of
testing needs to be confirmed.
Discussion of Progress
This topic will be addressed by ASME B31.12.
Recommendations
Standards must be established relating to hydrogen regulating
stations and pressure limiting systems. These standards must be incorporated by
reference into the federal code.
|